Introduction | |
---|---|
Boost and Trim Automatic Voltage Regulation (AVR) Gives higher application availability by correcting low and high voltage conditions without using the battery. Intelligent battery management Maximizes battery performance, life, and reliability through intelligent, precision charging. Power conditioning Protects connected loads from surges, spikes, lightning, and other power disturbances. Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature. Automatic restart of loads after UPS shutdown Automatically starts up the connected equipment upon the return of utility power. Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be replaced. Cold-start capable Provides temporary battery power when the utility power is out. Disconnected battery notification Warns when a battery is not available to provide backup power. Network manageable Provides remote management of the UPS over the network. Audible alarms Actively let you know if the unit is on battery, if the battery is low or if there is an overload condition. LED status indicators Quickly understand unit and power status with visual indicators. Serial Connectivity Provides management of the UPS via a serial port. USB connectivity Provides management of the UPS via a USB port (not available on all models). Disconnected battery notification Warns when a battery is not available to provide backup power. InfraStruXure Manager Compatible Enables centralized management via the APC InfraStruXureŽ Manager. User-replaceable batteries Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR). Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced. Predictive failure notification Provides early-warning fault analysis ensuring proactive component replacement. Resettable circuit breakers Enables a quick recovery from overload events. Adjustable voltage-transfer points Maximizes useful battery life by widening the input voltage window or tightening the output voltage regulation. Adjustable voltage sensitivity Provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications. Field-replaceable power distribution panel Ensures compatibility with equipment that has different plug types. |
|
Features | |
UPS topology | Line-Interactive |
Output power capacity | 1 kVA |
Output power | 640 W |
Waveform | Sine |
Input operation voltage (min) | 151 V |
Input operation voltage (max) | 302 V |
Input frequency | 50/60 Hz |
Surge energy rating | 480 J |
Noise level | 55 dB |
Surge protection | Y |
Audible alarm(s) | Y |
Ports & interfaces | |
AC outlet types | C13 coupler |
Power plug | C14 coupler |
AC outlets quantity | 4 AC outlet(s) |
Number of output IEC jumpers | 2 |
USB port | Y |
Serial interface | Y |
Serial interface type | RS-232 |
SmartSlot | Y |
Battery | |
Battery technology | Sealed Lead Acid (VRLA) |
Battery capacity | 216 VAh |
Typical backup time at full load | 5.4 min |
Typical backup time at half load | 14.5 min |
Battery life (max) | 6 year(s) |
Battery recharge time | 2 h |
Hot-swap battery | Y |
Automatic battery test | Y |
Design | |
Form factor | Rackmount |
Rack capacity | 1U |
Product colour | Black |
LED indicators | Battery replacement |
Certification | C-tick, CE, EN 50091-1, EN 50091-2, GOST, VDE, PEP, EOLI |
Operational conditions | |
Operating temperature (T-T) | 0 - 40 °C |
Storage temperature (T-T) | -15 - 45 °C |
Operating relative humidity (H-H) | 0 - 95% |
Storage relative humidity (H-H) | 0 - 95% |
Operating altitude | 0 - 3000 m |
Non-operating altitude | 0 - 15000 m |
Technical details | |
Sustainability certificates | RoHS |
Weight & dimensions | |
Width | 432 mm |
Depth | 660 mm |
Height | 44 mm |
Weight | 21.8 kg |
Package width | 559 mm |
Package depth | 775 mm |
Package height | 191 mm |
Package weight | 25.4 kg |
Packaging data | |
Rack mount kit | Y |
Cables included | RS-232, USB cable |
Manual | Y |
Software CD | Y |
Logistics data | |
Products per pallet | 8 pc(s) |
Other features | |
Interface | DB-9 RS-232, SmartSlot, USB |
Input connection type | IEC-320 C14 |
Nominal output voltage | 230 V |
Nominal input voltage | 230 V |
Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.